Facebook Google Plus LinkedIn Contact Us

| November 1, 2018

Fire Door Clearance Gauge

$9.99

6 in stock

Category:

Description

This handy fire door gap gauge is a great teaching tool for quickly checking fire door gap requirement compliance.

DOOR TO FRAME CLEARANCES:

  • WOOD DOOR: MAX 1/8” (NFPA 80 v2013 6.3.1.7.1)
  • STEEL DOOR: 1/8” +/- 1/16” (NFPA 80 v2013 6.3.1.7.1)

DOOR TO FINISHED FLOOR CLEARANCE:

  • ALL DOORS: 3/4″ (NFPA 80 v2013 4.8.4.1)
  • IF THRESHOLD IS ABOVE 38”: 3/8” (NFPA 80 v2013 4.8.4.2)

HOW TO USE THE CLEARANCE GAUGE:

  • With the door closed, measure from the pull side of the door.
  • Measure the clearance between the door and frame:
    1. Top
    2. Hinge Side
    3. Latch Side
  • Between the doors (when installed in pairs)
  • Measure the clearance between the door and finished floor.

Call Now to Get Started!

We offer fire safety services in Virginia and across the U.S.

(540) 650–3745

Facebook Google Plus LinkedIn Contact Us