This handy fire door gap gauge is a great teaching tool for quickly checking fire door gap requirement compliance.
DOOR TO FRAME CLEARANCES:
- WOOD DOOR: MAX 1/8” (NFPA 80 v2013 6.3.1.7.1)
- STEEL DOOR: 1/8” +/- 1/16” (NFPA 80 v2013 6.3.1.7.1)
DOOR TO FINISHED FLOOR CLEARANCE:
- ALL DOORS: 3/4″ (NFPA 80 v2013 4.8.4.1)
- IF THRESHOLD IS ABOVE 38”: 3/8” (NFPA 80 v2013 4.8.4.2)
HOW TO USE THE CLEARANCE GAUGE:
- With the door closed, measure from the pull side of the door.
- Measure the clearance between the door and frame:
- Top
- Hinge Side
- Latch Side
- Between the doors (when installed in pairs)